					General Specifications
					
						FS-400 Wall Strobe Operating
							| Operating temperature | 0°C to 50°C (32°F to 122°F) |  
							| Humidity range | 0% to 93% |  
							| Strobe flash rate | 1 Hz |  
							| Nominal Voltage | Regulated 24 VDC / 24 VFWR |  
							| Operating Voltage Range (RMS) | 16 to 33 |  
							| Input terminal wire gauge | 22 AWG to 12 AWG |  
							| Installation environment | For indoor use only |  RMS Currents (mA)
 
 
					
						
							| Candela | Regulated 24 VDC | Regulated 24 VFWR |  
							| 15 | 25 | 64 |  
							| 30 | 39 | 106 |  
							| 75 | 102 | 189 |  
							| 15/75 | 93 | 189 |  
							| 110 | 105 | 189 |  
							| 185 | 179 | 241 |  
					Candela Settings: 
 
					  | Light Output Dispersion 
 
					
						
							| Degrees
 | % of Candela Rating |  
							| Horizontal Dispersion | Vertical Dispersion, Wall to Floor |  
							| ±0 | 149 | 148 |  
							| ±5 | 146 | 149 |  
							| ±10 | 143 | 153 |  
							| ±15 | 138 | 135 |  
							| ±20 | 134 | 104 |  
							| ±25 | 128 | 101 |  
							| ±30 | 123 | 94 |  
							| ±35 | 116 | 92 |  
							| ±40 | 106 | 84 |  
							| ±45 | 99 | 75 |  
							| ±50 | 92 | 68 |  
							| ±55 | 87 | 65 |  
							| ±60 | 82 | 61 |  
							| ±65 | 78 | 58 |  
							| ±70 | 75 | 54 |  
							| ±75 | 73 | 49 |  
							| ±80 | 72 | 43 |  
							| ±85 | 81 | 40 |  
							| ±90 | 53 | 30 |  
							| Compound ±45° | 42 |  |  
 
					  |