•Unique ability to detect all four major elements of a fire
•Highest nuisance alarm immunity
•Advanced algorithms interpret and respond to the multiple inputs
•Six levels of sensitivity
•CO sensing for fastest response to slow-developing, smoldering fires
•Fully integrated infrared sensing to support the fire alarm decision
•Automatic drift compensation of smoke sensor and CO cell
•Superior EMI protection
•Twin LED indicators providing 360˚ visibility
•LEDs can be panel controlled to blink, latch on, latch off
•Built-in test switch
| Physical Specifications | ||
| Height | 2.7˝ installed in B210LP base or B501 base | |
| Diameter | 6.0˝ installed in B210LP base; 4.0˝ installed in B501 base | |
| Shipping Weight | 4.6 oz | |
| Color | Ivory | |
| Material | Bayblend FR110 | |
| Operating Humidity Range | 10 to 93% relative humidity (non-condensing) | |
| Application Temperature Range | 32°F to 100°F (0°C to 38°C) | |
| Electrical Specifications | ||
| Operating Voltage Range | 15 to 32 VDC | |
| Maximum Standby Current | 300 μA at 24 VDC (one communication every 5 seconds with LED blink enabled) | |
| Maximum Alarm Current (LED on) | 7mA at 24 VDC | |
| Sensitivity Settings and Suggested Applications | ||
| Level 1 | 1% / ft of smoke | Very clean environments – laboratories |
| Level 2 | 2% / ft of smoke | Clean environments – offices |
| Level 3 | 3% / ft of smoke | Moderately clean environments – hotel rooms, dorm rooms |
| Level 4 | 3% / ft of smoke with different algorithm processing and weighting of sensor elements | Hotel rooms near a shower, boiler rooms |
| Level 5 | 4% / ft of smoke | Equipment rooms, kitchens, paint shops |
| Level 6 | Thermal alarm at 135°F (57°C) | |
| *Once the CO cell has reached the end of life and enters Photo, Thermal, Infrared (PTIR) mode, the following sensitivities apply: | ||
| Level 1 | 1% / ft of smoke | Very clean environments – laboratories |
| Level 2 | 2% / ft of smoke | Clean environments – offices |
| Level 5 | 3% / ft of smoke | Moderately clean environments – hotel rooms, dorm rooms |
| Level 6 | Thermal alarm at 135°F (57°C) | |