General Specifications
| Operating temperature |
0°C to 50°C (32°F to 122°F) |
| Humidity range |
0% to 93% |
| Strobe flash rate |
1 Hz |
| Nominal Voltage |
Regulated 24 VDC / 24 VFWR |
| Operating Voltage Range (RMS) |
16 to 33 |
| Input terminal wire gauge |
22 AWG to 12 AWG |
| Installation environment |
For indoor use only |
FS-400 Wall Strobe Operating
RMS Currents (mA)
| Candela |
Regulated 24 VDC |
Regulated 24 VFWR |
| 15 |
25 |
64 |
| 30 |
39 |
106 |
| 75 |
102 |
189 |
| 15/75 |
93 |
189 |
| 110 |
105 |
189 |
| 185 |
179 |
241 |
CANDELA SETTINGS:

|
Light Output Dispersion
|
Degrees |
% of Candela Rating |
| Horizontal Dispersion |
Vertical Dispersion, Wall to Floor |
| ±0 |
149 |
148 |
| ±5 |
146 |
149 |
| ±10 |
143 |
153 |
| ±15 |
138 |
135 |
| ±20 |
134 |
104 |
| ±25 |
128 |
101 |
| ±30 |
123 |
94 |
| ±35 |
116 |
92 |
| ±40 |
106 |
84 |
| ±45 |
99 |
75 |
| ±50 |
92 |
68 |
| ±55 |
87 |
65 |
| ±60 |
82 |
61 |
| ±65 |
78 |
58 |
| ±70 |
75 |
54 |
| ±75 |
73 |
49 |
| ±80 |
72 |
43 |
| ±85 |
81 |
40 |
| ±90 |
53 |
30 |
| Compound ±45° |
42 |
|
|