Clean Agent Systems
Clean fire extinguishing agents include halon, halon replacements and inert gases. These gases are used in total flooding extinguishing systems to avoid lethal conditions for occupants given that the proper design and installation of such systems. The primary distinction between carbon dioxide and clean agents is the toxicity of the gas. Carbon dioxide extinguishing concentrations exceed its fatal limits while clean agents extinguishing concentrations are below their toxic thresholds. Halons have been identified as stratospheric ozone-depleting substances. As consequence of application of Montreal Protocol on Substances that Deplete Stratospheric Ozone, production of halons was ceased in developed countries by 1994. It’s currently being phased out in the last developing country that produces halons. Despite these facts, many halons systems remain in use worldwide. Recycled halons serve as source of supply for mobile military equipment, aviation application and explosion prevention application that remain dependent on halons. Currently, the transition to other forms of halon replacements is well underway. NFPA12A, Standard for Halon 1301 Fire Extinguishing Systems and NFPA2001, Standard on Clean Agent Fire Extinguishing Systems are published by the National Fire Protection Association (NFPA) to address halon, halon replacements and inert gases application in fixed systems. Clean fire suppression agents are defined as fire extinguishants that vaporize readily and leave no residue. Clean agent halon replacements fall into two categories:
- Compounds
- Inert Gases and Mixtures (e.g. nitrogen and argon, and blends of these)
- All are electrically nonconductive
- All vaporize readily and leaves no residue
- All are liquefied gases or display analogous behavior
- All can be stored and discharged from typical Halon 1301 hardware
- All use nitrogen super pressurization in most application for discharge purposes
- All are total flooding gases after discharge
- All are less efficient fire extinguishants than Halon 1301 with respect to storage volume and agent weight i.e. they require increased storage capacity.
- For the same fire type, size and discharge time, they all produce more decomposition products than Halon 1301.
The minimum extinguishing concentrations of total flooding systems for class A fires are determined as part of third-party approval process. Class B fires extinguishing concentrations are determined by the cup burner method. Total flooding systems are also used for explosion inerting. The inerting concentration is that required to prevent an acceptable pressure increase in a premixed fuel / air / agent mixture subjected to ignition source. Such systems employ rapid delivery of agent following very early detection of an ignition. These systems must be specifically designed for each application as there are no generic design requirements or standards available.
One of the main concerns when it comes to the use of clean agents in fire protection is the agent toxicity. Toxicology tests are performed based on:
- The duration and frequency of exposure
- Determination of specific biological effects
oxygen concentration of 12%).There are two main environmental impacts need to be considered with halocarbon clean agents
- Ozone depletion
- Global Warming
Clean agent systems methods of application are:
- Total Flooding Systems
These systems protect enclosed or at least partially enclosed hazards. They are either engineered systems or pre-engineered systems. Engineered systems are custom designed for each hazard using components approved for their broad performance characteristics. Such components may be arranged in almost unlimited variety of configurations. On the contrary, the number of components and configurations of a pre-engineered system is determined in advance and included in the description of the system approval. Total flooding systems are categorized into modular systems and central storage systems. The modular systems consist of single containers connected to discharge nozzles. These systems are often of less initial cost and high maintenance cost. Central storage systems locate all agent containers in one centralized location and use piping network to distribute the agent to discharge nozzles in various locations.
- The ability to extinguish shielded, obstructed, or three-dimensional fires in complex geometries
- The ability, using appropriate detector-based actuation, to extinguish fires at a very early stage, well before direct or indirect fire/smoke damage occurs
- The ability to cause no collateral damage due to agent discharge.
- Local Application Systems
All previously discussed systems and components are provided by Bavaria to satisfy the customers’ needs. Please check our products technical datasheets for more information or contact us.