Optimum for tank truck, bulk petroleum stations, large flow monitor & in Plant oil service
· The hose is of double jacket construction with 100% virgin spun polyester yarn in both jackets.
· For the 4" (102 mm) hose, there shall be a minimum of 13.0 filler yarns per inch in the inner jacket and 10.5 filler yarns per inch in the outer jacket. For the 5" (127 mm) hose, there shall be a minimum of 14.0 filler yarns per inch in the inner jacket and 10.0 filler yarns per inch in the outer jacket.
· The thickness of the lining shall be 0.020" (508 μm) minimum and it shall be constructed of extruded T.P.U. elastomer.
· The outside jacket shall be treated with ENCAPTM elastomer, which shall completely encapsulate the jacket fibers and not merely surface coat the jacket.
· The hose service temperature range shall be ‐60°F to 150°F (‐51°C to 66°C).
· FM abrasion test of 50,000 cycles minimum and Taber abrasion test of 15,000 cycles minimum.
· At 600 PSI (4200 KPa), its elongation shall not exceed 10% of the initial hose length, it shall not warp more than 12 inches (31 cm) and should not rise from the test table.
· The hose shall not twist more than 1 1/2 turn per 100 (30.5 m) while at 600 PSI (4200 KPa).
· Minimum service test pressure of 300 PSI (2100 KPa).
· Minimum proof test pressure of 600 PSI (4200 KPa).
· Minimum straight burst test pressure of 900 PSI (6300 KPa).
· The hose while curved to a radius of 27" (69 cm) shall not burst at less than 900 PSI (6300 KPa).
· Meets or exceeds ULC‐19 and NFPA 1961.
TablePerformance
Hose Size |
Minimum Kink Burst Test Pressure |
Service Test Pressure |
Proof Pressure |
Burst Pressure |
4" (102 mm) |
300 PSI (2100 KPa) |
300 PSI (2100 KPa) |
600 PSI (4200 KPa) |
900 PSI (6300 KPa) |
5" (127 mm) |
300 PSI (2100 KPa) |
300 PSI (2100 KPa) |
600 PSI (4200 KPa) |
900 PSI (6300 KPa) |