General Application From the smallest business to the largest facility or campus, small conventional panels feature large capacity power supplies and easy front panel programming while large intelligent systems lead the market in sophisticated features including distributed emergency audio and are remarkably easy to configure and program. In addition to systems, Secutron™ also offers the most complete line of advanced detection industry with the advanced system features required by emerging fire codes and new protection design practices. Large intelligent networked systems support fully redundant network modularity, graphic display annunciation/monitoring, building management system integration, programmable smoke control and multi-channel emergency communications across buildings, campuses or communities. Secutron™ systems are also supported with the largest selection of detectors, signaling devices and accessory devices, including intelligent power supplies. MMX Network Fire Dete
Input Power | ||||
120 VAC, 60 Hz | 2 A maximum |
Ratings are per transformer; one additional transformer may be added to increase capacity |
||
240 VAC, 50 Hz | 1 A maximum | |||
Mechanical | ||||
Overall Dimensions with Door | 16-7/8” W x 29-1/2” H x 5-1/4” D (429 mm x 749 mm x 133 mm) [see page 5 for mounting box detail] | |||
Environmental | ||||
Temperature Range | 32° to 120°F (0° to 49° C) | |||
Humidity Range | Up to 93% RH, non-condensing @ 90° F (32° C) maximum | |||
Signaling Line Circuit Ratings | ||||
Voltage | 24 VDC nominal, 27.5 VDC maximum | |||
Max. number of devices | MR-2100, Single SLC: 198 total, 99 detector, 99 control/monitor modules MR-2200, Dual SLCs: 396 total, 198 detectors, 198 control/monitor modules | |||
Compatible devices | Refer to list on page 5 | |||
Maximum line length | 3045 m (10,000 ft) (12 AWG, 3.31 mm2) | |||
Operation modes |
Available as Style 6 (Class A) or Style 4 ( Class B); T-tapping is allowed with Style 4 (Class B) connections only |
|||
Notification Appliance Circuit Output Circuits, Standard and Expansion NACs | ||||
NAC Output Ratings | 2 A maximum per NAC; 24 V full wave rectified DC output; power limited | |||
NAC Current, Standard with OneTransformer |
Total of NACs + Auxiliary Power = 2.5 A maximum (if Aux. Power Total = 500 mA; NAC power = 2 A maximum) |
|||
NAC Current with Optional Transformer |
Total NAC current = 7 A maximum Total of NACs + Auxiliary Power = 8 A maximum (optional transformer MR12VAC or MR24VAC) |
|||
Function Relay Output Circuits, Standard and Expansion Relays | ||||
All Relays | 2 A @ 30 VDC resistive; Form C contacts; requires power limited source | |||
Power Output Circuits | ||||
Auxiliary Power Outputs (two outputs) | Each output is rated 500 mA @ 24 VDC, filtered, regulated, and power limited; maximum ripple voltage=600 mVpp | |||
Battery Information | ||||
Battery Charger | current limited float charger for sealed lead acid batteries | |||
Float Charge | 27.5 VDC | |||
Charging Current | 2.7 A maximum, no auxiliary loads; 1.7 A nominal with 0.5 A on each Auxiliary output | |||
Maximum Battery Capacity |
12 Ah maximum size internal to cabinet; 35 Ah maximum size allowed, requires model MR2978 External Battery Cabinet |
|||
Communications Ports | ||||
ANN (annunciator port) | Fixed baud rate @ 4800 bps; for use with MR-2614 or MR-2644 Annunciators (refer to individual product Installation Instructions for capacities and wiring distances) | |||
RS-232-2 (MV-2700 or GRID) | Fixed baud rate @ 9600 bps; 20 ft (6m) maximum distance; for use with MV-2700 Voice Evacuation System or GRID Graphical PC Display | |||
CON4 (Dialer/City Module Port) | Fixed baud rate @ 4800 bps; for use with MRDL Digital Communicator Module or MRCTYB City Module | |||
J1 (Service port or serial printer port) | Fixed baud rate @ 9600 bps; 6 m (20 ft) maximum distance; for use with Service/Programming PC (using Windows 95 or 98); or for serial input printer | |||
Network Ports | ||||
COM1, COM2 (Secutron MR peer to peer network, redundant DCLR) |
Standard Protocol: 10km (33,000 feet; 6.2 miles) maximum distance between nodes, minimum 28 AWG wires (0.081 mm2); Total panel capacity varies with programmable baud rate: up to 254 panels with 9600, 4800, and 2400; up to 200 panels at 1200 RS-232 Protocol: up to 20 m (66 ft), typically for connection to external modem |
|||
Network Wiring Parameters (maximum line resistance = 680 ohms) |
Baud Rate 9600 4800 2400 1200 |
Maximum Capacitance 100 nF 220 nF 470 nF 680 nF |
Maximum Network Nodes 254 254 254 200 |
|