MR-2605R Five Zone Conventional Fire Alarm Control Panel

Applications:

General Application From the smallest business to the largest facility or campus, small conventional panels feature large capacity power supplies and easy front panel programming while large intelligent systems lead the market in sophisticated features including distributed emergency audio and are remarkably easy to configure and program. In addition to systems, Secutron™ also offers the most complete line of advanced detection industry with the advanced system features required by emerging fire codes and new protection design practices. Large intelligent networked systems support fully redundant network modularity, graphic display annunciation/monitoring, building management system integration, programmable smoke control and multi-channel emergency communications across buildings, campuses or communities. Secutron™ systems are also supported with the largest selection of detectors, signaling devices and accessory devices, including intelligent power supplies.

· Listed to UL 864, 9th edition
· 5 Style B (Class ‘B’) dual-use zones
· 2 Style Y (Class ‘B’) notification appliance circuits
· 6 Amp power supply
· 500mA of Aux. power
· Common alarm relay
· Common trouble relay
· Integral battery charger
·‘Secur-Bus’ for dialer and remote annunciation
· Event buffer
· Six programmable zone options
·  Class A capability, both NAC and Zones
· One-man walk test
· Programmable NAC silence timer
· 3 LEDs per zone
· Front panel programming
 
Optional Modules:
·City tie/polarity reversal module
· Relay module
· Style D (Class A) zone module
· Remote 5 zone LED annunciator
·  Flush trim ring
 

 

Specification:

AC Power 120V 60Hz 1.5A, 240V 50Hz
NAC 1 24 VDC full-wave rectified, 1.5A max., PTC overload protected, power limited, Style Y, (Class ‘B’)
NAC 2 24 VDC full-wave rectified, 1.5A max., PTC overload protected, power limited, Style Y (Class ‘B’)
NAC 1/2 as Style Z (Class A) 24 VDC full-wave rectified, 1.5A max., PTC overload protected, power limited
Zones 24 VDC filtered regulated, 60mAalarm current max., power limited,100 ohms max. line resistance
DAT/CLK Data and clock line for remote module communications. (Secur-Bus)
Aux+ 24 VDC filtered regulated, 500mA max., PTC overload protected, power limited
COM Non-switched return for AUX+ power, 500mA
SCOM Switched return for AUX+ power, 500mA
Note: The 500mA from AUX+ is shared between the COM and SCOM returns. Internal and remote module power is supplied from the AUX+ and COM supply.
Alarm relay contacts 30 VDC, 2A max.
Trouble relay contacts 30 VDC, 2A max.
Battery charger 24 VDC, 350mA max. Will charge up to 16AH* sealed lead-acid batteries max.
Cabinet 14 1/2” W x 15” H x 4 1/4” D - Red