From the smallest business to the largest facility or campus, small conventional panels feature large capacity power supplies and easy front panel programming while large intelligent systems lead the market in sophisticated features including distributed emergency audio and are remarkably easy to configure and program. In addition to systems, Secutron™ also offers the most complete line of advanced detection industry with the advanced system features required by emerging fire codes and new protection design practices. Large intelligent networked systems support fully redundant network modularity, graphic display annunciation/monitoring, building management system integration, programmable smoke control and multi-channel emergency communications across buildings, campuses or communities. Secutron™ systems are also supported with the largest selection of detectors, signaling devices and accessory devices, including intelligent power supplies.
Physical Specifications | ||
Height | 2.7˝ installed in B210LP base or B501 base | |
Diameter | 6.0˝ installed in B210LP base; 4.0˝ installed in B501 base | |
Shipping Weight | 4.6 oz | |
Color | Ivory | |
Material | Bayblend FR110 | |
Operating Humidity Range | 10 to 93% relative humidity (non-condensing) | |
Application Temperature Range | 32°F to 100°F (0°C to 38°C) | |
Electrical Specifications | ||
Operating Voltage Range | 15 to 32 VDC | |
Maximum Standby Current | 300 μA at 24 VDC (one communication every 5 seconds with LED blink enabled) | |
Maximum Alarm Current (LED on) | 7mA at 24 VDC | |
Sensitivity Settings and Suggested Applications | ||
Level 1 | 1% / ft of smoke | Very clean environments – laboratories |
Level 2 | 2% / ft of smoke | Clean environments – offices |
Level 3 | 3% / ft of smoke | Moderately clean environments – hotel rooms, dorm rooms |
Level 4 | 3% / ft of smoke with different algorithm processing and weighting of sensor elements | Hotel rooms near a shower, boiler rooms |
Level 5 | 4% / ft of smoke | Equipment rooms, kitchens, paint shops |
Level 6 | Thermal alarm at 135°F (57°C) | |
*Once the CO cell has reached the end of life and enters Photo, Thermal, Infrared (PTIR) mode, the following sensitivities apply: | ||
Level 1 | 1% / ft of smoke | Very clean environments – laboratories |
Level 2 | 2% / ft of smoke | Clean environments – offices |
Level 5 | 3% / ft of smoke | Moderately clean environments – hotel rooms, dorm rooms |
Level 6 | Thermal alarm at 135°F (57°C) |