Products Details

FH-400 Wall Mount

Applications:

General Application From the smallest business to the largest facility or campus, small conventional panels feature large capacity power supplies and easy front panel programming while large intelligent systems lead the market in sophisticated features including distributed emergency audio and are remarkably easy to configure and program. In addition to systems, Secutron™ also offers the most complete line of advanced detection industry with the advanced system features required by emerging fire codes and new protection design practices. Large intelligent networked systems support fully redundant network modularity, graphic display annunciation/monitoring, building management system integration, programmable smoke control and multi-channel emergency communications across buildings, campuses or communities. Secutron™ systems are also supported with the largest selection of detectors, signaling devices and accessory devices, including intelligent power supplies.

•Compact Design
•Lower power consumption per device allows for more notification appliances per circuit and reduces the need for external power supplies
•Multiple field-selectable audible settings
--Temporal, Continuous, March Time and 20 BPM audible tones
--High and Low volume settings
•Wall and ceiling-mount
•Red or white finish
•Device settings are located on the back of the unit to prevent tampering
•Includes shorting clip that allows installers to test the wiring before the device is installed
•Supports 12 to 22 AWG
•Mount to Mircom BB-400 surface mount back box, single gang, 4-inch square, double gang, octagon and 4-inch junction boxes
•All units include universal mounting plate
•For indoor applications.
 
Compliance:
•UL 464
•ULC-S525
 


General Specifications:

 
Operating temperature 0°C to 50°C (32°F to 122°F)
Humidity range 0% to 93%
Nominal Voltage Regulated 24 VDC / 24 VFWR
Operating Voltage Range (RMS) 16 to 33
Input terminal wire gauge 22 AWG to 12 AWG
Installation environment For indoor use only

Audible Ratings

dBA Reverberant Ratings per UL464 (dBA@10 ft)

Sound Pattern  
Volume
16
VDC
Reg. 24 VDC 33
VDC
16
FWR
Reg. 24 FWR 33
FWR
 
Temporal
High 82.2 84.9 84.6 76.8 79 80
Low 75.5 80.5 80.2 71.8 75.1 76.6
 
Continuous
High 86.4 89.2 88.7 81.5 83.1 84
Low 79.9 84 84.8 76.2 79.3 81.2
 
20 BPM
High 79 81.3 81.6 74 75.1 76.1
Low 72.3 76 76.7 68.9 71.7 73.3
 
March
High 83.2 86.4 85.7 79.2 80.6 81.4
Low 76.9 80.9 81.7 73.3 76.2 78

dBA Anechoic Ratings per CAN/ULC-S525 (dBA@3 m)
Sound Pattern  
Volume
16
VDC
Reg. 24 VDC 33
VDC
16
FWR
Reg. 24 FWR 33
FWR
 
Temporal
High 90.2 93.2 93.2 84.4 87.1 88.5
Low 83.7 87.4 88.3 78 82.2 84.5
 
Continuous
High 90.2 93.2 93.3 85.1 87.8 89
Low 83.8 87.6 88.6 78.5 83 85
 
20 BPM
High 90.3 92.9 92.9 84.4 87.2 88.6
Low 83.6 87.3 88.3 78 82.2 84.5
 
March
High 90.2 92.9 92.9 84.4 87.1 88.4
Low 83.7 87.4 88.3 78 82.2 84.4

 

 

 

FH_400 horn operating RMS currents (mA)
 
 
Volume
Reg. 24 VDC,
all tones
Reg.
24 VFWR,
all tones
High 37 31
Low 22 25
 
ULC Directional Sound  Characteristics
Horizontal Axis
± 45° -3 dbA
± 61° -6 dbA
± 90° -10 dbA
Vertical Axis
± 49° -3 dbA
± 61° -6 dbA
± 90° -7.7 dbA