Products Details

MPD-65P Photoelectric Smoke Detector

Applications:

General Application From the smallest business to the largest facility or campus, small conventional panels feature large capacity power supplies and easy front panel programming while large intelligent systems lead the market in sophisticated features including distributed emergency audio and are remarkably easy to configure and program. In addition to systems, Secutron™ also offers the most complete line of advanced detection industry with the advanced system features required by emerging fire codes and new protection design practices. Large intelligent networked systems support fully redundant network modularity, graphic display annunciation/monitoring, building management system integration, programmable smoke control and multi-channel emergency communications across buildings, campuses or communities. Secutron™ systems are also supported with the largest selection of detectors, signaling devices and accessory devices, including intelligent power supplies.

• Wide operating voltage range
• Advanced electronics technology
• Flashing standby/steady alarm LED
• Magnetic test switch
• Low profile (1 5/8”H x 4”Dia.)
• Can be used on security systems
• Locking feature reduces tampering
• Designed to meet approvals worldwide
• Large range of bases available
• Separate head/base design allows interchangeability and ease of installation
• High RF, noise and insect immunity
• Available in 2 and 4 Wire Kits


 Specifications:
MPD-65P Photoelectric Smoke Detector
 
 
Features
Red Flashing Clear LED in Standby / Magnetic Test Switch
Supply Voltage 9 to 33VDC
Average Current                       
Standby 24VDC 45μA
(Without accessories) 9VDC 40μA
Alarm 24VDC 52mA
(Without accessories) 9VDC 17mA
Alarm Indication Steady on Red LED
Ambient Temperature -4°F to 140°F (-20°C to 60°C)
(No Condensation or Icing)
Nominal Sensitivity 2.5%/ft.
Max Wind Continuous Not Affected