From the smallest business to the largest facility or campus, small conventional panels feature large capacity power supplies and easy front panel programming while large intelligent systems lead the market in sophisticated features including distributed emergency audio and are remarkably easy to configure and program. In addition to systems, Secutron™ also offers the most complete line of advanced detection industry with the advanced system features required by emerging fire codes and new protection design practices. Large intelligent networked systems support fully redundant network modularity, graphic display annunciation/monitoring, building management system integration, programmable smoke control and multi-channel emergency communications across buildings, campuses or communities. Secutron™ systems are also supported with the largest selection of detectors, signaling devices and accessory devices, including intelligent power supplies.
Voltage Range | Thermal Ratings | ||
15 - 32 volts DC peak | Fixed Temperature Setpoint: 135°F (57°C) Rate of Rise Detection: 15°F/min. (8.3°C/min.) High Temperature: 190°F (88°C) | ||
Standby Current | |||
Ion/Thermal: 150 uA @ 24 VDC (without communication, LED off) 200 uA@ 24 VDC (one communication every 5 sec. with LED enabled) |
|||
Operating Temperature Range | |||
Ion/Photo: 32°F to 120°F (0°C to 49°C) Photo with Thermal: 32°F to 100°F (0°C to 38°C) Thermal: -4°F to 100°F (-20°C to 38°C) High Temperature: -4°F to 150°F (-20°C to 66°C) Pinnacle: 32°F to 100°F (0°C to 38°C) |
|||
Photo/Photo with Thermal: 250 uA @ 24 VDC (without communication, LED off) 300 uA@ 24 VDC (one communication every 5 sec. with LED enabled) |
|||
Pinnacle: 230 μA @ 24VDC (without communication) 330 μA @ 24VDC (one communication every 5 sec. with LED enabled) |
|||
UL Listed Velocity Range | |||
Ion: 0 - 1200 fpm (0 - 6.1 m/sec) Photo/Photo with Thermal: 0 - 4000 fpm (0 - 20 m/sec) Pinnacle: 0 - 4000 fpm (0 - 20 m/sec) |
|||
LED Current (max.) | |||
6.5 mA @ 24 VDC (on) | |||
Insect Screen Hole Size | |||
Height | |||
Photo: 0.016 inch (0.41mm) nominal Ion: 0.035 inch (0.89mm) nominal | |||
2.0 inches (51 mm) 1.66 inches (42 mm) - Pinnacle |
|||
Self Diagnostics (PinnacleTM) | |||
Diameter | |||
Initiated by control panel Activated by test magnet | |||
6.1 inches (155 mm) Installed in B210LP Base 4.1 inches (104 mm) Installed in B501 Base 4.0 inches (102 mm) - Pinnacle |
|||
Smoke Sensitivity (PinnacleTM) | |||
9 levels: 0.02, 0.03, 0.05, 0.10, 0.20, 0.50, 1.00, 1.50, 2.00%/ft. obscuration (0.06, 0.10, 0.16, 0.33, 0.66, 1.65, 3.24, 4.85, 6.41%/m obscuration) |
|||
Shipping Weight | |||
Heat: 4.8 oz. (137 g) Photo/Photo with Heat: 5.2 oz. (147 g) Ion: 5.4 oz. (154 g) Pinnacle: 5.6ox. (159 g) |
|||
Drift Compensation (PinnacleTM) | |||
High sensitivity maintenance alert signal Low sensitivity maintenance alert signal Maintenance urgent signal | |||
Relative Humidity | |||
10% - 93% non condensing | |||
B224RB/B224BI Electrical Ratings
|