From the smallest business to the largest facility or campus, small conventional panels feature large capacity power supplies and easy front panel programming while large intelligent systems lead the market in sophisticated features including distributed emergency audio and are remarkably easy to configure and program. In addition to systems, Secutron™ also offers the most complete line of advanced detection industry with the advanced system features required by emerging fire codes and new protection design practices. Large intelligent networked systems support fully redundant network modularity, graphic display annunciation/monitoring, building management system integration, programmable smoke control and multi-channel emergency communications across buildings, campuses or communities. Secutron™ systems are also supported with the largest selection of detectors, signaling devices and accessory devices, including intelligent power supplies.
Operational Specifications | ||
Protection Range | 16 ft to 328 ft (5 m to 100 m) | |
Adjustment Angle |
±10 Degrees horizontal & vertical (The optics move independent of the unit) |
|
Sensitivity Levels |
Level 1 – 25% Level 2 – 30% Level 3 – 40% Level 4 – 50% Acclimate™ Level 1 – 30 to 50% Acclimate Level 2 – 40 to 50% |
|
Fault Condition (Trouble) |
96% or more obscuration blockage In alignment mode Improper initial alignment Self-compensation limit reached |
|
Alignment Aid |
Optical gunsight Integral signal strength indication 2 digit display |
|
Alarm Indicator | Local red LED and remote alarm | |
Trouble Indicator | Local yellow LED and remote trouble | |
Normal Indicator | Local flashing green LED | |
Test/Reset Features |
Integral Sensitivity Test Filter (BEAM200S only, requires additional external power supply) Sensitivity filter (Incremental scale on reflector) Local test switch Local reset switch Remote test and reset switch (Compatible with RTS151 and RTS151KEY test station) |
|
Smoke Detector Spacing |
On smooth ceilings, 30 to 60 feet between projected beams and not more than one- half that spacing between a projected beam and a sidewall. Other spacing may be used depending on ceiling height, airflow characteristics, and response requirements. See NFPA 72 and CAN/ULC S524. | |
Environmental Specifications | ||
Temperature | –22°F to 131°F (–30°C to 55°C) | |
Humidity | 10 to 93% RH Noncondensing | |
Electrical Specifications | ||
Voltage | 15 to 32 VDC | |
Avg. Standby Current (24VDC) | 2 mA Max | |
Avg. Current During Testing | 500 mA Max | |
Alarm Current (24VDC) | 8.5 mA Max | |
Fault Current (24VDC) | 4.5 mA Max | |
Alignment Mode Current (24VDC) | 20 mA Max | |
Mechanical Specifications | ||
Detector Dimensions | 10 in H × 7.5 in W × 3.3 in D (254 mm H × 191 mm W × 84 mm D) | |
Reflector Dimensions (16′ to 230′) | 7.9 in × 9.1 in (200 mm × 230 mm) | |
Reflector Dimensions (beyond 230′) | 15.7in×18.1in(400mm×460mm) | |
Electrical Specifications (BEAMHK) | ||
Voltage | 15 to 32 V | |
Current | 92 mA at 32 V | |
Power Consumption | 1.6 W at 24 V; 3 W at 32 V | |