• Aerospace Industry - Hydroxy fuels, Hydrogen and Hydrazine fuels • Aircraft Hangars - landing gear pits, under-wing and over-wing protection • Automotive - manufacturing, paint spray booths • Chemical Industry - production, storage, transportation • Paint - manufacturing facilities • Petrochemicals - production, storage, shipping facilities • Pharmaceutical Industry • Polymers and Glue - manufacturing and curing • Power Generation Facilities - pump areas, gen- erator rooms, unmanned stations, gas-fired and coal-fired reactors • Printing Industry - solvent handling, presses, drying processes • Warehouses - storage facilities for flammable materials
Spectral Response | UV: 0.185 - 0.260 microns. IR: 2.5 - 3 microns | |||
Detection Range | ft m | ft | m | |
(Highest Sensitivity Setting for 1 ft2 (0.1m2) pan fire) | Gasoline 50 15 Methanol | 25 | 7.5 | |
n-Heptane 50 15 Methane | 15 | 5 | ||
Diesel Fuel 37 11 LPG Propane | 15 | 5 | ||
JP5 37 11 Hydrogen* | 15 | 5 | ||
Kerosene 37 11 Silane | 15 | 5 | ||
(Alcohol Ethanol 25 7.5 Polypropylene Pellets | 15 | 5 | ||
IPA (Isopropyl Alcohol) 25 7.5 Office Paper | 12 | 4 | ||
20،± (0.5m) long 8،± (0.2m) width plume fire | ||||
Response Time | Typical 5 sec. | |||
Adjustable Time Delay | Up to 30 sec. | |||
Field of View | 100¢ horizontal, 100¢ھ vertical | |||
Built-in-Test | Manual and Automatic BIT | |||
Temperature Range | Operating: -40¢F (-40¢ھC) to 160¢ھF (70¢C) | |||
Storage: -65F (-55¢ھC) to 185¢ھF (85¢C) | ||||
Humidity | Up to 95% |