Products Details

LW Series Foam Chambers

Applications:

Williams LW series foam chambers are used as Type II discharge devices. They are installed in flammable liquid storage tanks perimeter to discharge low expansion foams on burning liquids surfaces.

LW Series Foam Chambers consist of a foam expansion chamber and an integral foam maker, defined by NFPA 11 as “Type II” top-side application device.  The foam chamber is installed inside a flammable liquid storage tank above the product’s highest liquid level.  The chambers are designed to meter foam flow, then gently expand and deliver foam directly onto the surface of a flammable or combustible liquid. The foam solution is piped to the chamber from outside the hazard area.  Upon entering the chamber, the foam solution is expanded and then discharged against a deflector inside the storage tank. The deflector directs the foam against the inside wall of the storage tank. This reduces the submergence of the foam and agitation of the fuel surface. In operation, foam solution passes through an orifice plate which is sized to deliver the required flow rate at a specific inlet pressure. The metered flow of foam solution is then introduced into the foam maker, where it is aerated. The foam chamber inlet piping is fitted with a frangible vapor seal, which is designed to rupture at a predetermined pressure. The aerated foam solution enters the foam expansion chamber body, where additional expansion occurs, and the velocity of the foam is reduced. As the foam leaves the chamber body, it passes through the tank shell, and then impacts the foam deflector, which directs the foam down the tank wall and ultimately onto the fuel surface. Foam deflectors are available in either split (as a standard) or shallow configurations. Split-style deflectors allow for installation when the deflector location is only accessible from outside the tank (existing tank installations), but can be used elsewhere. Shallow style deflectors are useful when only a small space between the foam dam or tank rim is available and a normal deflector may come into contact with part of the floating roof. All foam chambers are supplied with standard finish, primed with red epoxy exterior coating.

  LW Series Foam Chamber Models

Model Nominal Flow Inlet Flange Outlet FlangeL
LW-9 40 – 150 gpm (151 – 568 Lpm) 2.5” 4”
LW-17 100 – 280 gpm (379 – 1,060 Lpm) 3” 6”
LW-30 190 – 600 gpm (719 – 2,271 Lpm) 4” 8”
LW55 400 – 1,000 gpm (1,514 – 3,785 Lpm) 6” 10”
 
  Notes:
  Operational inlet pressure for foam chambers is 50 psi (3.4 bars) to 100 psi (6.9 bars). Pressures outside of thatrange require engineering approval.

  Product Specifications:
  
Materials of Construction
Body, Maker and Flanges  Carbon Steel
Retainer Hatch Stainless Steel and Brass
Orifice Plate Stainless Steel
Retainer, Vapor Seal Brass