BAVARIA HFC-227 Engineered Systems are used for total flooding application to extinguish Class A,B and C fires in accordance with NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems and UL listed design and installation manual.
Molecular Weight | 170.03 |
Boiling Point @ 760 mm Hg, °C | -16.4 |
Critical Temperature, °C | 101.7 |
Critical Pressure, kPa | 2912 |
Critical Density, kg/m3 | 621 |
Vapour Pressure @ 20 °C, bar | 4.57 |
Freezing Point, °C | -131.1 |
Viscosity of Liquid @ 25 °C, centipoises | 0.184 |
Solubility of Water in Agent @ 21, % By weight | 0.06 |
Specific Heat of Liquid @ 25 °C, kJ/kg °C | 1.184 |
Heat of Vaporization @ Boiling Point at 25 °C, kJ/kg | 132.6 |
Component | % By Weight | Tolerances |
HFC 227ea | 99.85 | ±0.1 |
Isopropenyl-1methyl cyclohexene | 0.15 | ±0.05 |
Agent Purity, mole %, minimum | 99.0 |
Acidity, ppm (by weight HCI equivalent), maximum | 3.0 |
Water content, % by weight, maximum | 0.001 |
Non-volatile residues, gram/100 ml maximum | 0.05 |
Environmental Factor | HFC-227 | Halon 1301 |
Ozone Depletion Potential, CFC 11=1 | 0 | 12 |
Global Warming Potential, CO2 Kg – 100 years | 3220 | 6900 |
Atmospheric Lifetime, years | 33 | 65 |