• UL and C-UL listed
• 12 VDC with 15, 35 or 60 cd settings
• 24 VDC with 15, 35, 60, 75, 95 or 110 cd settings
• 6 distinct candela settings
• Candela selection view window
• 15/75 ADA compliant on 60cd setting
• 33 sound output settings
• Horn or chime sound output
• Pre-wire back plate
• Universal back plate mounting (single gang, double gang, octagon, or 4” square)
• Single screw mounting
• For indoor applications
Specifications:
Strobe Current
| Light Output |
Max. RMS Operating Current (mA RMS) | |||
| Reg. 12 VDC | Reg. 12 FWR | Reg. 24 VDC | Reg. 24 FWR | |
| 15cd | 116 | 152 | 62 | 99 |
| 35cd | 209 | 267 | 102 | 152 |
| 60/75cd | 254 | 258 | 131 | 190 |
| 75cd | NA | NA | 146 | 208 |
| 95cd | NA | NA | 177 | 243 |
| 110cd | NA | NA | 196 | 268 |
| Voltage | 12/24V | |
| UL Designation | Regulated 12 DC/FWR | Regulated 24 DC/FWR |
| Operating Voltage Range | 8 – 17.5V | 16 – 33V |
| Flash Rate | 60 times/min. | |
| Sync Module (SDM-240) | N/A | Available |
| Operating Temperature Range |
Indoor model: 32°F to 120°F (0°C to 49°C) | |