Inline Foam Eductors provide the simplest and most economical method of introducing a metered flow of foam concentrate into a pressurized water stream. As opposed to “Hydro-Foam™ Technology” which is used in union with master stream nozzles, these “Venturi-Type” foam proportioners are designed to be used in conjunction with a matched constant flow end-of-line device (e.g., nozzle), where adequate water pressure is available. The pressurized water stream creates a vacuum (the Venturi effect) which is used to suck foam concentrate into the eductor body. The dosing of the concentrate is controlled by either an orifice plate or a metering valve. The concentrate enters and mixes with the water stream. The foam solution exits through the outlet of the inductor.
Ordering Information:
| Part Number | Nominal Flow @200 psi (13.8 bars) | Inlet Size | Outlet Size |
| 15738 | 60 gpm (227 Lpm) | 1.5” | 1.5” |
| 11841 | 95 gpm (360 Lpm) | 1.5” | 1.5” |
| 11842 | 95 gpm (360 Lpm) | 2.5” | 1.5” |
| 15983 | 125 gpm (473 Lpm) | 1.5” | 1.5” |
| 14707 | 250 gpm (946 Lpm) | 2.5” | 2.5” |