• Listed to UL 864, 9th edition.Available in six and twelve zone models
• Available in LED and LCD Display configurations
• LCD Display versions are equipped with a 2 line by 20 character back-lit LCD display and numerical
keypad
• Integrated UDACT/Digital Communicator on select models
• Front panel and PC programmable
• LED Display versions are front panel (using CFG-300 configuration tool) and PC programmable
• Remote upload/download capabilities
• Base panel is equipped with Class “B” (Style “B”) initiating circuits which may be configured as Class “A” (Style “D”) using a Class “A” converter module
• Initiating circuits may be configured as Alarm, Verified Alarm, Waterflow Alarm, Sprinkler Alarm, Latching or Non-Latching Supervisory, Monitor and Trouble- Only
• Base panel is equipped with Class “B” (Style “Y”) indicating circuits which may be configured as Class “A” (Style “Z”) using a Class “A” signal converter module
• Audible signals may be configured for Steady, Temporal Code, California Code and March Time
• Indicating Circuits may be configured as Silenceable or Non-Silenceable for both signals and strobes
• Built-in sync protocols for the following strobe manufacturers: Mircom, Amseco, System Sensor,
Gentex, Faraday and Wheelock
• Relay contacts for Common Alarm, Auxiliary/Alarm (Disconnectable), Common Supervisory and Common Trouble
• Configurable Signal Silence Inhibit, Auto Signal Silence and One-Man Walk Test
• Subsequent Alarm, Supervisory, and Trouble operation
• RS-485 Interface for Remote LED Annunciators, LCD Annunciators and Remote Smart Relay Modules
• Two event history logs comprised of a 200 event alarm log for alarm related events and a 200 event general log for all other events
• 5 Amp Power Supply
• Optional modules for additional internal relay circuits and City Tie/Polarity Reversal
• Optional trim rings for semi-flush mounting
 
                              
                         
                         
                        
                            
                                
	
		
			| 
				AC Input  | 
			
				120VAC @ 60Hz  | 
		
		
			| 
				Standby Power  | 
			
				24VDC standby batteries  | 
		
		
			| 
				Charging Capability  | 
			
				4 to 12 AH  | 
		
		
			| 
				Indicating Circuits  | 
			
				Power limited / 24VDC unfiltered / 1.7A @ 49°C per circuit. Maximum 5 Amps. | 
		
		
			| 
				Unfiltered supply (full wave rectified) | 
			
				Power limited / 24VDC unfiltered / 1.7A max at 49°C  
				  | 
		
		
			
				Auxiliary Relays (Common alarm/supv/trb/ and auxiliary second alarm)  
				  | 
			
				FormC / 28VDC / 1A max 
				  | 
		
	
	
		
			| 
				Current Consumption  | 
		
		
			| 
				Model | 
			
				Standby | 
			
				Alarm | 
		
		
			| 
				MR-2306-DDR  | 
			
				142 mA (112 mA*)  | 
			
				312 mA (282 mA*)  | 
		
		
			| 
				MR-2312-DDR  | 
			
				174mA (104 mA*)  | 
			
				444mA (394 mA*)  | 
		
		
			| 
				MR-2312-LDR  | 
			
				164mA (104 mA*)  | 
			
				424mA (364 mA*)  |