Fire Alarm Control
	• One expandable to nine Intelligent Signaling Line Circuits
	(SLC)
	• Modular design
	• Each SLC is capable of supporting 159 Analog Sensors and
	159 Addressable Modules which can be wired in Style 6 or
	7 (Class A) or Style 4 (Class B)
	• Four Style Z/Y (Class A/B) Notification Appliance Circuits
	rated at 1.7 Amps each
	• System has the ability to mix CLIP and AP devices on the
	same loop
	• Large 4 by 20 character Back-lit LCD Display with user
	friendly menu
	• Supported languages: English, French, Arabic* and Hebrew*
	(*960 character back-lit LCD display only)
	• Correlatable Switch Inputs which allow for multi-functional
	outputs
	• Four Status Queues with selector switches and LEDs for
	Alarm, Supervisory, Trouble and Monitor
	• Auxiliary relay contacts for Common Alarm, Common
	Supervisory and Common Trouble
	• Group bypass with built-in false alarm prevention technology
	• RS-232 output for remote system printer or CRT
	• Two Event History Logs comprised of a 6000 event alarm
	history log for alarm related events and a 6000 event log
	for all events
	• Supports three configuration files (current, previous and next
	configuration) with “hot swap” support
	• Supports Conventional Hardwire Adder Modules
	• Built-in One Man Walk Test operation
	• Configurable for Canadian Two Stage operation
	• Configurable for Coded Operation
	• Capability to adjust Intelligent Smoke Detector sensitivity
	levels
	• Real time 3D graphical monitoring and control using Open
	Graphic Navigator™
	• BACnet support
	• Supports Boolean logic functions
	• Built-in Ethernet port
	• Remote diagnostics via a built-in web server
	• UL listed for Smoke Control
	 
	Network Features
	• Up to 63 nodes
	• Peer-to-peer network communications
	• Style 4 (Class B) or Style 6 or 7 (Class A) wiring configuration
	• Proprietary Arcnet Network Communications protocol
	• Supports copper and/or fiber optic network cable